Study of Earth-Fault Location Method for Distribution Network Based on Transient Signal

According to the generating process and propagation characteristics of earth-fault transient signal, an earth-fault location method for distribution network based on transient signal is presented. In the method, in order to change line characteristic impedance, a resonant filter circuit is paralleled in line segment border, so that it could cause transient current energy differences in feature frequency band on both sides of detection device. The location method achieves earth-fault area location through comparing transient current energy and energy attenuation coefficient in feature frequency band. The simulation test result shows that the method isnt influenced by distribution system grounded style, operation style and other factors and which could detect the earth-fault area rapidly and reliably in distribution network and has a high project application value.

Distribution network Transient signal Earth-fault Fault location Energy

Zhi Chao Huang Yi Zhong Cai Lin Li Mu Liu Sheng Zhen Yang

Guilin University of Electronic Technology,Guilin,Guangxi,541004,China

国际会议

2011 International Conference on Vibration,Structural Engineering and Measurement(2011年振动、结构工程与测量国际会议 ICVSEM 2011)

上海

英文

742-746

2011-10-21(万方平台首次上网日期,不代表论文的发表时间)