会议专题

Simulation Study of Single Line-to-Ground Faults on Rural Teed Distribution Lines

Teed lines are widely used in rural power networks in China. The paper theoretically analyzes the voltages and currents when a single line-to-ground fault occurs, constructs a new mathematical model for fault location on the teed lines, performs corresponding MATLAB simulations. Simulation results show that currents near the source (bus M) are almost independent of fault posi-tions and fault resistances. However, voltages at bus M are sensitive to fault positions while fault voltages at fault position are only sensitive to transient resistances. A novel approach to fault location on teed lines is proposed. First, the faulted line is identified with remote control equipment. Then, the transient resistances are calculated according to the fault voltages. And at last, the fault distances are computed according to the voltages at bus M and the calculated transient resistances.

simulation fault location teed line single line-to-ground fault

Wanying Qiu

School of Basic Sciences, East China Jiaotong University, Nanchang, P. R. China

国际会议

The 4th IFIP International on Computer and Computing Technologies in Agriculture and the 4th Symposium on Development of Rural Information(第四届国际计算机及计算机技术在农业中的应用研讨会暨第四届中国农业信息化发展论坛 CCTA 2010)

南昌

英文

521-524

2010-10-22(万方平台首次上网日期,不代表论文的发表时间)