会议专题

Experimental Study on Simplified Thermo-technical Calculation for Evaporative Coolers

Evaporative cooling is energy efficient and environment protective. However, little research has been done on the simplified and applied thermotechnical calculation method. In order to improve the practicability and advantage of evaporative cooling unit, and make the unit manufacture standard, a thermo-technical calculation for a plate indirect evaporative cooling unit and a packing direct evaporative cooling unit are simplified by experiments base on engineering optimization theory. In the experiments, an optimal water-spraying density was gained for the packing direct evaporative cooling unit, with the aluminum foil packing specific surface area of 500m2/m3; as well as an optimal waterspraying density for plate indirect evaporative cooling unit, with primary air channel length of 4mm, and secondary air channel length of 6mm.

evaporative cooling air conditioning thermo-technical calculation design water-spraying density

Zhang Dan Zhao Wei

School of Civil and Architectural Engineering Liaoning University of Technology Jinzhou, China

国际会议

2011 IEEE 2nd International Conference on Computing,Control and Industrial Engineering(CCIE 2011)(第二届计算、控制与工业工程国际会议)

武汉

英文

348-351

2011-08-20(万方平台首次上网日期,不代表论文的发表时间)