Research on Rotary-gas High Voltage SF6 Circuit Breaker with Novel Blade Nozzle Part II: Motion Behavior Analyses under Cold Flow Interruption
A 252kV single-break SF6 circuit breaker (CB) is taken as the investigation model in this paper, and six different nozzles with different blade contour and 3D gas flow field model are presented based on NS equations. And the variations of the cold flow field parameters in arc-quenching chamber with different nozzles have been obtained using finite volume method (FVM) during the interrupting. The influences of blade contour on the gas flow parameters, such as velocity, pressure-temperature ratio and pressure are analyzed by changing the angle, number and the height of the blade. And the reasonable nozzle blade structure of the rotary-gas CB is obtained.
Yundong Cao Shu Wang Xiaoming Liu Zhiming Qi
School of Electrical Engineering, Shenyang University of Technology, 110870, Shenyang, P.R.China Liaoning Branch of Extra-high Voltage Company, 114001, Anshan, P.R.China
国际会议
西安
英文
131-134
2011-10-23(万方平台首次上网日期,不代表论文的发表时间)