会议专题

Experimental Research on the Comparison of the Arc Characteristics Between DC 270V and DC 28V

In order to fulfill the increasing need for high electric power and to decrease the weight of electrical equipments, the supply level must be increased and the electrical apparatus has to be upgraded accordingly. In our present work, experiments are carried out to compare the arc characteristics on break between DC 28V and DC 270V under the conditions of different current and transverse magnetic fields (TMF). The current is lower than 10A, and the flux density is below 100mT. Arc images are acquired with high speed cameras and arc voltage waveforms are obtained. Arc characteristics such as arc duration, extinction gap, displacement of arc root are analyzed. Experiment results show that under the same break power, TMF is more effective in arc inhibition under the condition of DC 270V compared with DC28V. The work can offer some guide for the design of arc extinction system for DC 270 V relays.

Yaqi LIU Xinglei CUI

School of Electrical Engineering and Automation Harbin Institute of Technology, Harbin, 150001, China

国际会议

2011 1st International Conference on Electric Power Equipment-Switching Technology(第一届电力设备开断技术国际会议 ICEPE)

西安

英文

652-656

2011-10-23(万方平台首次上网日期,不代表论文的发表时间)