COMPARISON OF DC ICING FLASHOVE PERFORMANCES FOR PRE-POLLUTED SHORT SAMPLES OF COMPOSITE INSULATORS WITH DIFFERENT CONFIGURATION IN HIGH ALTITUDE AREA
DC icing flashover performance of seven types of pre-polluted short samples of composite insulators at low air pressure simulated by the multifunction artificial climate chamber was researched in this paper. The rationality of the minimum sample size of the improved U-type method used in the paper was proofed. The test results show that the relationship between DC icing flashover gradient and air pressure meets power function and the value of the exponent n describing the influence of air pressure is 0.397 to 0.711 for the 7 types of insulators. The influences of sheds configuration parameters, ice thickness, pollution and air pressure on icing flashover performance were analyzed. And the selection of sheds configuration of UHV DC composite insulators in high altitude was suggested.
Jiang Xingliang Muhammad Tariq Nazir Chao Yafeng Chen Ling Bi Maoqiang Zhang Zhijin Sun Caixin
State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing 400030, China