CALCULATION STUDY ON ICE-MELTING IMPLEMENTATION STRATEGY OF TRANSMISSION LINES

Technology characteristics of AD/DC-based de-icing is analyzed. The general finite element method (FEM) code ANSYS is employed to establish the unit model and calculate the stress situation of tower in different de-icing ways of wires. In this paper, researchers propose the AD/DC-based de-icing implementation strategy and set the ice critical thickness as 70% of design value and no more than 20mm, to control ice-melting implementation. When the ice thickness meets or exceeds 90% of design value, AD-based de-icing technology should be applied as much as possible.

Liu Chun Xie Yi Lu Jiazheng Jiang Zhenglong

Hunan Electric Power Test and Research Institute, Changsha, China, 410007