会议专题

The performance Test and Analysis of Heat Recovery Type Heat Pipe Indirect Evaporative Cooling Air-Conditioning Unit

Combining the heat recovery technology of heat pipe and evaporative cooling technology, this article researched a heat recovery heat pipe-type indirect evaporative cooling air-conditioning unit and tested this unit. Based on analyzing we got main perfoprmance factors and best operation parameters. The best ratio of volume of secondary air and primary air is 0.8, the best water delivery is 0.322 m3/h, the efficiency of heat pipe-type indirect evaporative cooler is 70.39 %.This research provided reliable reference for the research and development of air-conditioning unit.

Xiang Huang Sheng WU Chao Wang Jun-mei WU Li-juan Fan

Xian Polytechnic UniversitySchool of Environmental and Chemical EngineeringXi’an 710048, Shaanxi, C Xian Polytechnic University School of Environmental and Chemical Engineering

国际会议

The 4th International Conference on Bioinformatics and Biomedical Engineering(第四届IEEE生物信息与生物医学工程国际会议 iCBBE 2010)

成都

英文

1-4

2010-06-18(万方平台首次上网日期,不代表论文的发表时间)