Study on Thermal Efficiency of Gas-Fired Vacuum Hot Water Boiler with Installing Flue Gas Condensing Waste-Heat Exchanger
Gas-fired vacuum hot water boiler with installing a flue gas condensing waste-heat exchanger was taken as the research object, through theoretical analysis and calculation with respect to energy saving and emission reduction to the boiler which heating load was 69.78kW, the boiler thermal efficiency could be increased by 6.6% and the emissions of CO2 could be decreased by 0.34 m3/h after setting the flue gas condensing waste-heat exchanger. It had no corrosion to flue duct and no pollution to atmospheric environment after through desulphurization treatment to the gas, so the boiler had great economic and social benefits.
Pan Zhixin Niu Jianhui Lu Chunping Zhang Zhihong Zhu Junjun
Department of Urban Construction, Hebei Institute of architectural Engineering Zhangjiakou, China Zhu Junjun BeiJing KD Navien Heat Energy Equipment Co.,LTD
国际会议
成都
英文
1-4
2010-06-18(万方平台首次上网日期,不代表论文的发表时间)