会议专题

SEISMIC FRAGILITY STUDY FOR HIGH-PRESSURE EMERGENCY COOLING WATER TANKS OF LOVIISA NUCLEAR POWER PLANT

The paper studies the fragility of high-pressure emergency cooling water tanks in Loviisa Nuclear Power Plant located on the elevation+25.40 in the reactor building. The seismic fragility is defined as the conditional probability of its failure given a value of the response parameter, such as peak ground acceleration. Using the lognormal-distribution assumption, the fragility (i.e., the probability of failure, f) at any nonexceedance probability level Q can be derived as Equation 1 f’=Φ(ln(a/A)+βUΦ-1 (Q))/βR where Q=P(f < f|a) is the probability that the conditional probability f is less than f for a peak ground acceleration a. A is the median ground acceleration capacity, βR is the logarithmic standard deviation representing the randomness about A, and βU is the logarithmic standard deviation representing the uncertainty. The quantity Φ(.) is the standard Gaussian cumulative distribution function. In order to assess the fragility of the tanks the strain time histories for tank supports and piping nozzles were calculated using the joint structural-equipment model. The ground motion response spectra shape used in the structural response analysis has been taken from the YVL 2.6 - guide 1. This shape represents the envelope spectrum for Southern Finland corresponding to the median annual frequency of 10-5. The sampling of the model properties was carried out with the aid of the Latin hypercube sampling method. In order to find the failure modes the strain time histories were calculated for the piping nozzles and for support structures of the tanks. Since strain is the best measure of energy absorption, energy limited events need to be based on the strain acceptance criteria. The adopted failure limit is the cumulated plastic strain of 8% in the tank sheet metal or in the supporting structures. This failure limit has taken from the reference 2. The end result of the study is the presentation of the median fragility curve for the tanks as well as 95% and 5% fractile curves.

Jukka K(a)hk(o)nen Pentti Varpasuo

FORTUM Ltd POB 100, FI-00048 FORTUM, Finland

国际会议

18th International Conference on Nuclear Engineering(第18届国际核能工程大会 ICONE 18)

西安

英文

1-6

2010-05-17(万方平台首次上网日期,不代表论文的发表时间)