会议专题

A New Method for Identifying the Fault Location on Series Compensated Lines Based on Transient Fault Information

Based on the transient circuit model of series compensated line,a new method for identifying the fault location relative to series capacitor (SC) is proposed.Comparing the transient model of series compensated line when fault occurs before the SC and the one when fault occurs after the SC,it is found that the only difference is the value of a model-parameter: it respectively equals 0 and a large value under the two circumstances.This method using transient data at several sample points after fault occurs calculates the model-parameter to identify the fault location.Since only the transient information before MOV operation is used,MOVs nonlinear characteristic neednt to be considered.The method is applicable to both single phase to earth fault and phase to phase fault.Moreover,communication channels can be saved for only locally derived information is used.The validity of the method is proved by simulating results.

series compensated lines:fault location:MOV transient information:model-parameter identification

Yuxue Wang Xianggen Yin Zhe Zhang Jinrui Tang Zhiqin He

Electrical Power Security and High Efficiency Lab Huazhong University of Science and Technology Wuhan,Hubei,430074,China

国际会议

2011 4th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies(第四届电力设施管制、重建及能源技术国际会议 DRPT 2011)

威海

英文

78-82

2011-07-06(万方平台首次上网日期,不代表论文的发表时间)