The Disturbance Source Identification of Forced Power Oscillation Caused by Continuous Cyclical Load

The continuous cyclical load disturbances can lead to forced power oscillations of power systems.Based on the single-machine infinite-bus system,the differences in the energy conversion characteristics between the forced power oscillation and the weak damping free oscillation are analyzed and the mechanism of the forced power oscillation caused by cyclical load disturbances is presented.Using energy functions with the linear equations of motion of the rotor,the basic principles to identify the cyclical load disturbance source location of the forced power oscillation are analyzed in energy perspective.The simulation results of the New England 10-machine 39-bus system indicate the feasibility and validity of the proposed method.

Low frequency oscillation:Forced power oscillation:Energy function:Continuous cyclical load Disturbance source identification

Yiping Yu Yong Min Lei Chen Ping Ju

College of Energy and Electrical Engineering,Hohai University,Nanjing,China State Key Lab.of Power Systems,Dept.of Electrical Engineering,Tsinghua University,Beijing,China

国际会议

2011 4th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies(第四届电力设施管制、重建及能源技术国际会议 DRPT 2011)

威海

英文

308-313

2011-07-06(万方平台首次上网日期,不代表论文的发表时间)