会议专题

Study on the the Unsubstantial Locations Index for Voltage Sags

This paper implements an unsubstantial location index(ULI) for evaluating the voltage sag impacts of the fault locations in power system on the customer.Three stochastic simulation models of fault locations are compared before proposing the index to get the most accurate simulation model.The ULI is presented considering both the remnant magnitude of voltage sags and frequency of the faults in the system.Monte Carlo simulation method is applied in simulating the voltage sag events.With the results of ULI,the sequence provides the most important location that needs to be considered.The ULI can tell the utility which points need to be taken care of,and help them make decision in the schedule of reconstruction.

Power Quality Voltage Sags Monte Carlo Methods

Qing Zhong Yao Zhang Lingxue Lin Zhigang Wu Jinming Yang

Electrical Engineering College,South China University of Technology,Guangzhou,510640,China Electrical Engineering College,South China University of Technology Department of Electrical Engineering,the Hong Kong Polytechnic University,Hong Kong Zhejiang University,China University of Technology

国际会议

2011 4th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies(第四届电力设施管制、重建及能源技术国际会议 DRPT 2011)

威海

英文

410-416

2011-07-06(万方平台首次上网日期,不代表论文的发表时间)