Integration of Wind farm into Power System Using VSC-HVDC Transmission System
In this work,wind farm with VSCHVDC connected to the grid are developed including wind side grid converter,grid side converter,DC cable and the emulated circuit control model.During fault in the AC grid DC link voltage increases rapidly and this would cause the HVDC link to trip for over voltage.To solve this problem,the location of the AC fault can be transferred to the wind farm side by reducing the voltage at the wind farm side HVDC converter terminal.This method is called the emulated short-circuiting of the wind farm side HVDC controller.To validate the models and conclusions,PSCAD/EMTDC is used.The simulation results show that the DC voltage level on HVDC line is maintained constant by using the proposed emulated short circuit control model.
VSC-HVDC:DFIG:Neutral Point Diode clamped:Emulated short-circuiting
KONE Ibrahima Chengyong Zhao
School of Electrical and Electronics Engineering North China Electric Power University Beijing,CHINA
国际会议
威海
英文
477-484
2011-07-06(万方平台首次上网日期,不代表论文的发表时间)