会议专题

Application of bidirectional power converters to overcome some disadvantages of a SVC substation in Thainguyen, Vietnam

The analysis results on the operation of reactive power compensators in the Thainguyen power substation in Vietnam show their positive effect on the power system.They have a part in maintaining the voltage at the connection points (220/110/23 kV substation) that equals to the setting value U* according to the requirements of the Vietnamese power system dispath center.However,there are still some disadvantages of this substation that need to be overcome: the large number of main devices,much harmonics generated,and very high active power loss.Thus,the author has an idea to solve these problems by application of a bidirectional power converter (BDPC) using a decoupling controller in order to compensate the reactive power corresponding to the setting voltage.The benefit of this new solution is to eliminate the three above fundamental disadvantages.The research results have been verified by simulations in Matlab/Simulink software.

Dr. Ngo Duc Minh

Department of electric power systems Thainguyen University of Technology (TNUT) Thainguyen,Vietnam

国际会议

2011 4th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies(第四届电力设施管制、重建及能源技术国际会议 DRPT 2011)

威海

英文

509-513

2011-07-06(万方平台首次上网日期,不代表论文的发表时间)