会议专题

Impacts of large scale integration of wind power on power system small-signal stability

In this paper,based on a small-size power system,a deterministic assessment on the impact of wind power on power system small-signal stability is first thoroughly discussed.Next,a realistic weak wind-hydro-thermal (WHT) power system is used to ascertain if the indicative findings of the preliminary work can be confirmed by a large scale case study.Subsequently,Monte Carlo based probabilistic eigenanalysis is implemented on the weak WHT system in order to further corroborate the findings drawn from the deterministic studies.It was found out that large wind power integration can have positive or negative impacts on system damping depending on the location of the wind power plant,the amount of the conventional generation replaced by wind power and the stress level of the power system.

Small-signal stability:eigenanalysis:wind power doubly-fed Generator

José L. Rueda István Erlich

Institute of Electric Power Systems University Duisburg-Essen Duisburg,Germany

国际会议

2011 4th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies(第四届电力设施管制、重建及能源技术国际会议 DRPT 2011)

威海