会议专题

Technology Research for Flexible Control System of Neutral-Point Ground Impedance for Distribution Networks

As the power network appeared fault,the residual fault-current can be controlled under the allowed range by using the traditional Petersen-coil to compensate the most part of capacitive current.Although the small residual fault-current can also cause gas explosion in mining power supply system with high reliability.A novel control technology of neutral-point ground impedance is presented in the thesis by controlling the duty cycle of power electronics IGBT,The ground impedance control systems are with reactor continue changing,excellent dynamic responding,high control precision and the residual fault-current approaching zero,it can reduce the accident probability.Theoretical derivation and MATLAB simulation results show that the proposed method is with high precision,high speed and noiselessness.It can improve distribution automation,accelerate grounding fault arc self-extinguishing,and enhance power quality.

Distribution system:Fault-current:IGBT:mining power supply system

Yi Wentao Li Sukang

power dispatching center Nanchang Power Supply Company Nanchang,Jiangxi,China

国际会议

2011 4th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies(第四届电力设施管制、重建及能源技术国际会议 DRPT 2011)

威海

英文

1216-1220

2011-07-06(万方平台首次上网日期,不代表论文的发表时间)