Study on a Real Case of Low Frequency Oscillation Occurred in the Black-Start by a Hydropower Plant
This paper recaptures a low frequency oscillation occurred during simulation and finally being resolved in the real grid.Three hypothesis are proposed to tackle this issue,namely the ferro-resonance caused by hasty stepping up,the inrush current derived from remanence in transformer and the parameter resonance between the unit and experiment grid.After being refuted consecutively it is assumed that the autoexcitation system parameter resonates with grid.Expectedly the oscillation vanished by altering the control parameter with proof of some simulation results.At last two conclusions are presented from experimental analysis.
low frequency oscillation:parameter resonance excitation system:stepping up from zero:black-start
Bo YANG Jing JIANG Tao YU Jinliang JIANG
dept.of Electric Power South China University of Technology GuangZhou,China
国际会议
威海
英文
1445-1448
2011-07-06(万方平台首次上网日期,不代表论文的发表时间)