Research on Detection for Compensation Current of Three Phase Unbalance Load Compensation
This paper presents a novel compensation current detection approach for DSTATCOM under unbalanced conditions based on the improved instantaneous symmetrical components. The principle of the proposed approach is based on the real-time rotating vector which enables calculate the positive sequence component,negative sequence component and zero sequence component of the three phase instantaneous variables. The problem of traditional symmetrical components is solved by using the proposed method. The novel current detection is tested by means of detailed simulation using PSCAD/EMTDC,where the performance is validated in the case of severe network fault and in the case of unbalanced load compensation. The results verify the improved instantaneous symmetrical component is more suitable for compensation current detection.
instantaneous symmetrical components rotary vector current detection unbalanced
Fan Feng Rui Dong Qing-fu Xiong
Zhengzhou Power Supply Company,Zhengzhou,450052,China
国际会议
南京
英文
30-35
2010-09-13(万方平台首次上网日期,不代表论文的发表时间)