An Improved Fault Locating System of Distribution Network based on Fuzzy Identification

Fault locating system,which is designed for the fast power recovery,is very important in the economical operating of the distribution network. But,for the uncertainty of the fault information,the incorrect conclusion may be obtained by the traditional fault location calculation,so the most fault locating system can not be employed in the distribution network. In this paper,an improved fault locating system is proposed,which is composed of the fault signal acquisition unit and the fault location analysis center. Fuzzy identification is employed in the fault location analysis center to deal with the uncertainty of fault information. The failure and mistake rates of indicator action are used as the fuzzy parameters to calculate the fuzzy difference of the fault sequence and the standard fault set. The fault indicator is the primary device of fault information acquisition. The radio frequency and GPRS technology construct the communication channel of fault signal acquisition unit,which cuts down the construction cost and also ensures the obtaining accuracy of the fault information. The fault location system is working on the distribution network and operating well. With the accurate fault location,power supply recovers fast. The loss of power failure is reduced effectively.

Fault locating system Fuzzy identification Radio frequency GPRS DTU

Xiaohui Zhu Xin Lu Dong Liu Bingda Zhang

Tianjin Electric Power Research Institute,Tianjin,China School of Electrical Engineering & Automation,Tianjin University,Tianjin,China

国际会议

2010年中国国际供电会议(CICED 2010)

南京

英文

115-120

2010-09-13(万方平台首次上网日期,不代表论文的发表时间)