Comparison and Selection of High-voltage Large-capacity D-STATCOM Main Circuit

In view of analysis and comparison of present high-voltage large-capacity D-STATCOM circuit structure,especially advantages and disadvantages of Δ-cascaded structure and Y-cascaded structure,then it proposes and describes a Y-cascaded structure,the link of which is composed of two back-to-back H converters. Current compensation algorithm based on coordinate αβ conversion,fault links bypass tolerance,and its correlative CPS-SPWM are proposed respectively,the experimental results of 1.14kV/100kVA prototype testify the validity and the effectivity of the proposed structure and algorithm.

D-STATCOM Y-cascaded structure fault-tolerance neutral shift

Zhen-yu Yang Sheng Xu Xing-tao Xu

Substation Operation Center,Changzhou Power Supply Company,Changzhou 213003,China School of Matter Network Engineering,Jiangnan University,Wuxi 214122,China Information Center,Taizhou Power Supply Company,Taizhou 225300,China

国际会议

2010年中国国际供电会议(CICED 2010)

南京

英文

443-449

2010-09-13(万方平台首次上网日期,不代表论文的发表时间)