Measurement based on the group linear regression method of harmonic impedance
Harmonic pollution monitoring and control is the key to an accurate estimate of harmonic impedance,and thus an accurate assessment of public connection points of the harmonic emission level. This paper analyzes the link under the star-shaped and triangular three-phase asymmetrical power systems derived established a three-phase unbalanced power system harmonic impedance matrix estimation model. Model is based on a large number of systems and load the public connection point of the simulation data,the real and imaginary part of the harmonic impedance by opening and using grouping multiple linear regression method,on the system side harmonic impedance matrix to estimate the value of each element. Simulation and error analysis shows that the model obtained more accurate and effective.
Three-phase asymmetry harmonic impedance harmonic admittance multiple linear regressions
Wang lei Yu bo
Shanghai university of electric power 2103,Pingliang Rd,Shanghai;Shanghai extra voltage power transmission company.SMEPC,wuning Rd,shanghai
国际会议
南京
英文
508-614
2010-09-13(万方平台首次上网日期,不代表论文的发表时间)