会议专题

Very fast over voltage simulation and analysis in 500kV GIS substation of Xiangshuijian pumped storage power station

Based on the power system simulation software DIgSILENT,this paper presents the Electro-Magnetic Transient (EMT) simulation of Very Fast Transient Overvoltage (VFTO) phenomena in 500kV GIS substation of Xiangshuijian pumped storage power station. The modeling of GIS components and its connected equipments are summarized. The operation of disconnector in GIS under different typical substation configurations is simulated. It is concluded that the highest VFTO level in the GIS substation is below 500kV substation Lightning Impulse Withstand Voltage (LIWV). The influence factors of VFTO are studied in this paper,including transformer entrance capacitance,residual charge of GIS bus conductor and the cable length between GIS and transformer. The variation regularities of VFTO level with these factors are concluded.

Very fast transient over voltage insulation coordination DIgSILENT GIS disconnector electro-magnetic transient simulation

Shujie SUN Meiqi YAO

AREVA T&D China Technology Center,Building 6,No188 Xinjun Ring Rd,Minhang District,Shanghai,PR.China 201114

国际会议

2010年中国国际供电会议(CICED 2010)

南京

英文

757-762

2010-09-13(万方平台首次上网日期,不代表论文的发表时间)