会议专题

Comprehensive Application of Signal Injection method in Protection and Control of MV Distribution System

In MV distribution system,signals need to be injected regularly or when the single phase-to-ground fault occurs while distributed capacity measurement,fault line selection and fault location techniques based on signal injection are applied. In order to prevent mutual interference of different signals,reduce equipment investment and simplify wiring,the comprehensive application based on signal injection in protection and control of MV distribution system is proposed. In this paper,optimal signal frequency,signal injection mode and signal detection mode which can be shared are chosen by taking carrier based islanding protection as research object and taking the applications of distributed capacity measurement,fault line selection and fault location techniques based on signal injection into comprehensive consideration.

Signal injection distributed capacity measurement fault line selection fault location carrier based islanding protection

Fan Shuxian Xu Bingyin

Shandong University,Jinan 250061,China Shandong University of Technology,Zibo 255049,China;Shandong Kehui Power Automation,Co.,Ltd,Zibo 255

国际会议

2010年中国国际供电会议(CICED 2010)

南京

英文

934-940

2010-09-13(万方平台首次上网日期,不代表论文的发表时间)