Harmonic Suppression and Reactive Control of NQ Station in Genan HVDC System
This article has analyzed the origin and the harm of harmonics in the HVDC system. The harmonics analysis has been done to the DC and AC side of NQ substation in Ge-Nan HVDC system. And found the order 13 harmonic filters capacities are insufficient,so DA32 capacitor group will be transformed into HP11.8 filter. The reactive power control method of NQ station is also introduced in this paper,especially Umax,Q-control and Qmax control algorithms. The tests validated the AC filter switching sequence. The reason of F1 group filters must be devoted firstly before the HVDC system starts is analyzed.
harmonics RPC HVDC AC filter switching
YANG Guang-liang TAI Neng-ling WANG Yong
Department of Electrical Engineering,Shanghai Jiao Tong University,Shanghai 200240,China;Shanghai El Department of Electrical Engineering,Shanghai Jiao Tong University,Shanghai 200240,China Continuing Education School,Shanghai University of Electric Power,Shanghai 200433,China
国际会议
南京
英文
1380-1387
2010-09-13(万方平台首次上网日期,不代表论文的发表时间)