Energy Saving Control Method Research of Modular Water Chillers Group Operation and Pump Variable-Frequency Control Based on
According to a ward office building air conditioning system historical operation data, this article analyzed the number of air-conditioning cooling load operation, the time frequency and air conditioning systems circulating water temperature difference trend with air-conditioning load; proposed 4:2:4 group control method to the modular water chillers and air-conditioning water system energy-saving control scheme of variable frequency plus constant temperature difference. Energy-saving control system using Programmable Logic Controller (PLC) as the core controlling device was built, control logic was programmed. The running experiments show a remarkable energy-saving rate of 26.1%, with good energy efficiency and economy effects.
energy saving control strategy grouped control variable-frequency control dynamic load requirements analysis air conditioning system
Tian Peizhe Wang Fenglan
Biochemical Engineering College Beijing Union University Beijing, China Shili Air Conditioning Technology Development Co.,Ltd.Beijing, China
国际会议
长春
英文
192-195