会议专题

The Measure of Customer Equipment Failure Event Due to Voltage Sag

An effective evaluation method of sensitive equipment failure event in customer side is proposed. In this method, the voltage sag severity and maximum entropy principle are used to present the voltage sag severe degree and its probability distribution. The voltage sag duration and magnitude with certain physical performance are converted to severity indices namely sag duration severity index (DSI) and voltage magnitude severity index (MSI). Based on maximum entropy principle, the probability distribution functions of sag severity indices are calculated without any assumption. Cumulative summing method is used to determine the probability of customer equipment failure event As a case study, the personal computer is simulated and the results show that this method is reasonable and accurate.

voltage sag customer equipment sensitivity failure event sag severity maximum entropy principle assessment method

Xiaoqing Huang Miao Li

Sichuan Electric Vocational and Technical College Chengdu 610065,China

国际会议

Third International Conference on Information and Computing(第三届信息与计算科学国际会议 ICIC 2010)

无锡

英文

31-35

2010-06-04(万方平台首次上网日期,不代表论文的发表时间)