To Features of Heat Pumps Development for Work in Russian Climate Conditions
The air heat pump (HP) driven from GTP, created on the basis of aircraft gas turbine engine (GTE) with expired airworthiness life, is considered. HP uses outdoor air from negative (-40℃) up to positive (+ 15℃) temperature as a low-grade heat source and provides heating temperature in a range from 100 to 220℃ with performance factor 2.5-3.2. The high technological burning of gas decreases its discharge for heating on the average in 1,5 times in comparison with usual boiler-house. Cold exhaust of HP with temperature about -40... -70℃ feeds both in the driving gas turbine plant (GTP) and in a connected for electric energy generating GTP, that increases their specific power and efficiency. In standard HP, designed for work with low-grade heat source from + 5 to + 10℃, the heating temperature is not exceed 60-65℃for the referred performance factors.