Experimental Study on Heat Transfer of Plate Heat Exchanger and Application to Waste Heat Power Generation
According to investigation on the steel plant, a large amount of low thermal energy is emitted directly to the environment without any utilization. It is apparent that energy cogeneration and energy conversion become a problem concerned by all countries. At present, the utilization of thermal energy stored in slag washing water is mainly confined to transformation to heating rather than electricity generation. The working mechanism of electricity generation using slag washing water and experimental study on heat transfer characteristics of plate heat exchanger are presented in this paper. The experimental results show the non-linear relationship between heat transfer coefficient of plate heat exchanger made by different materials and different flow velocity of clean water in the pipe. When the flow velocity is greater than 1m/s, K retains a certain value while the resistance coefficient increases dramatically. By comparison of experimental data, it is found that the heat resistance outside plate heat exchanger is the main factor that influences performance of plate heat transfer.
Slag Washing Water Heat Transfer Plate Heat Exchanger Waste Heat Power Generation
X.Y.Tang D.S.Zhu C.Q.Guo
Key Lab of Enhanced Heat Transfer and Energy Conservation, the Ministry of Education, School of Chemistry and Chemical Engineering, South China University of Technology, Guangzhou, PR China
国际会议
西安
英文
442-445
2009-07-11(万方平台首次上网日期,不代表论文的发表时间)