Study of isolated power system with generator and inverter power source

Application of new power generations such as photovoltaic generation and full cell is increasing recently due to problem of global warming and resources depletion. These new power generations are connected always a large ac power system and operated with their control like a constant active power control. In future, the operation of isolated power system disconnected from the existing ac power system will be considered. We assume the isolated power system consists of synchronous generator and inverter power source. In this paper the stable operation of the isolated power system is studied in viewpoint of how larger capacity of the inverter power source compared to the capacity of the synchronous generator can be connected. Result of simulation shows that the capacity of the inverter power source less than or equal to five times of the generator gives stable operation.

synchronous generators Inverters Stability criteria