会议专题

Fault Current Distribution in Transmission and Distribution Systems with Shield Wires, Neutral Wires and Cable Sheaths

The fault current distribution among various paths, such as shield wires, neutral wires, cable sheaths, electric line structure grounds, and substation or power plant grounding systems, is computed and analyzed for several scenarios. A parametric analysis of the effects of several key variables on the fault current distribution is carried out. The variables include: cross section of power lines, length of power lines, tower footing resistance, grounding system resistance, type of static wires, and soil resistivity. In this paper, the fault current distribution and electromagnetic interference levels have been studied and evaluated for a typical electrical network with overhead and underground cable lines. Furthermore, a measure has been provided to effectively reduce interference to acceptable levels.

Electromagnetic interference fault currents grounding power cables power distribution lines transmission lines

J. Liu F. P. Dawalibi J. Ma S. Fortin

Safe Engineering Services & technologies ltd, 3055 Blvd. Des Oiseaux, Laval, Quebec, Canada H7L 6E8

国际会议

The International Conference on Electrical Engineering 2009(2009 电机工程国际会议)

沈阳

英文

1-6

2009-07-05(万方平台首次上网日期,不代表论文的发表时间)