A Simulation of Arc Generation at AC-DC Neutral Section of Electric Railway
This paper provides an experimental and theoretical analysis of the arc discharges generated between contact wire and pantograph of high speed railway. A video-based arc detection device is installed on the KTX train, and arc discharges are measured for a 45.87km track section of high speed railway in Korea. It is measured that the rate of contact loss is 0.3% which is lower than the regulated value of 1.0% for high speed train, and arc discharges induced by 21 small size contact losses and 6 medium size contact losses occur continuously along the track. The power of arc discharge between contact wire and pantograph is calculated as 9.0~22.5kW which is approximately onehundredth of that of the arc discharges generated at the neutral section of contact wire. The results of the measurement and the analysis suppose that a study be followed to suppress arc discharges and contact wire damages for the safe operation of high speed railway.
Electric railway arc discharge contact loss contact wire pantograph neutral section