Research On The Over-voltage of 220kV Power System Caused by Traction Transformers Commissioning
The over-voltage of 220kV power system appeared during the commissioning of several traction transformers in Jilin Province. Analysis showed that the electromagnetic oscillating of the system caused the over-voltage of the feeding phases. After setting up an accurate simulating model used in ATP-EMTP,the adverse influence on the electric power system and the character of the oscillation over-voltage had been studied. Results showed that under the environment of these substations the amplitude of the over-voltage couldnt exceed 2.0p.u and would have little influence on electric power system.
Oscillating over-voltage Transformer Simulating study
Cheng Fangxiao Sun Ying Ma Weiping
Changchun University of Technology No.17 Yanan Road,Changchun,China Jilin Electric Power Research Institute No.4433 Renmin Street,Changchun,P.R.China
国际会议
2009 9th International Conference on Electronic Measurement & Instruments(第九届电子测量与仪器国际会议 ICEMI2009)
北京
英文
1684-1688
2009-08-16(万方平台首次上网日期,不代表论文的发表时间)