会议专题

Screw Chillers Model Suitable for Variable Operating Condition

For predict the performance of screw chillers working at variable operating conditions, a simulation model based on TRNSYS was presented. Based on the primary physics,fluid and heat transfer theory, the sonmodels including the compressor, shell and tube condenser, and f looded evaporator were present.Taken TRNSYS as the simulation platform, a simulation of a chillers was completed. Compared the prediction and experimental value, the errors are within ±8%.The results show that the model has high accuracy and are suitable for simulation at part-load.

Screw chillers Part-load Model Variable operating condition

Xiaoqiang Jiang Weiding Long

School of Machine Engineer,Tongji University,Shanghai,China School of Engineer,Guangdong ocean unive Sino-German School of Applied Sciences,Tongji University of Shanghai,China

国际会议

The 6th International Symposium on Heating,Ventilating and Air Conditioning(第六届国际暖通空调学术会议)

南京

英文

336-342