A Study of the Ground Source Heat Pump System in Shanghai Minhang Archives in the Heating Mode

The ground source heat pump (GSHP) system installed in Shanghai Minhang district archives, consisted of two water-to-water heat pumps, 280 boreholes with 80 m depth is the first archives project installing the GSHP system in China. Because of the specialization of the archives which demands a steady temperature and humidity, the system has to run all the years. The experimental study in winter shows that the COP of the heat pump is 5.2 and the average temperature and relative humidity of the archives house are 22.8℃ and 52.5%, respectively.

Ground source heat pump Heating mode Archives house temperature Archives house relative humidity Performance of heat pump

Xin Yu Ruzhu Wang Xiaoqiang Zhai

lnstitute of Refrigeration & Cryogenics,Shanghai Jiao Tong University,Shanghai,China