会议专题

Performance Simulation of Condensing Heat Ezchanger in Different Work Conditions

This article aims to provide a more accurate calculation method for design of condensing heat exchanger (CHX) through an in-depth discussion about work conditions of the CHX commonly used in temperature and humidity control system. With difference of the simplified configuration of CHX, a mathematical model is given. Specifically, the Log-mean temperature difference (LMTD) method is used in dry conditions, while in wet conditions mass and energy conservation equations are used. The set of equations of the model are solved by using the shooting method provided by Matlab/Simulink program. The results of work conditions and the performances of heat transfer and dehumidification of CHX are determined. Analysis shows that the simulation model can evaluate performances of the CHX in different work conditions reasonably and the results are close to the physical phenomenon. The method raised in this paper is valuable for design and optimization of CHX.

Condensing heat ezchanger Temperature and humidity control system Simulation Matlab/Simulink Environmental control system

Jing Wang Weixing Yuan Xiugan Yuan

Dept.of Man-Machine-Environmental Engineering,Beihang University,Beijing,China

国际会议

The 6th International Symposium on Heating,Ventilating and Air Conditioning(第六届国际暖通空调学术会议)

南京

英文

708-715

2009-11-06(万方平台首次上网日期,不代表论文的发表时间)