Characteristic of Ultrafiltration on Treatment surface-water in China
Ultrafiltration membrane (UF) was employed in water treatment for raw water of Yangtze River and water supply. The results showed that the UF filtration system is not suitable to treat raw water in Zhenjiang segment of Yangtze River without any pre-treatment. Whether the quality of raw water is good and not, it is very important to select suitable backwash period during filtration of membrane system to reduce the pollution of membrane. In this study, the relationship of resistance of membrane with filtration time, reversible and irreversible resistance by pure water backwash and intrinsic resistance of membrane could be calculated respectively by controlling the operation condition. The irreversible resistance increases with the filtration time, which made membrane become contaminated easily and caused membrane difficult to be recovered. And it will be used as a reference to direct the practical application of UF technology in Water Purification Plant.
Conventional treatment Ultrafiltration (UF) Transmembrane pressure (ΔP) Fluz Fouling Resistance of membrane
Weiying Li Bingzhi Dong
Key Laboratory of Yangtze Aquatic Environment, Ministry of Education College of Environmental Science and Engineering, Tongji University Shanghai: 200092, P.R.China
国际会议
上海
英文
3323-3327
2008-05-16(万方平台首次上网日期,不代表论文的发表时间)