Application of FEM for Understanding the Electric Field Distribution in Copper Sulphide Contaminated Paper-Oil Insulation of Power Transformer

Power transformers are failing due to the formation and migration of copper sulphide in to paper insulation. The copper sulphide is formed due to the interaction of sulphur present in the oil with copper conductor. This paper presents FEM simulation of the copper sulphide contaminated model of paper oil insulation and analysis of the consequent field distortions. The results indicate increase in electric stress across paper insulation due to field distortion. An effort is made to validate the experimentally obtained partial discharge inception voltages.

Power and converter transformer corrosive sulphur Finite Element method (FEM) Partial discharge (PD)

Rudranna N V.Krishnan J.Sundara Rajan

Department of Electrical and Electronics Engineering, R.V.College of Engineering, Bangalore, 560059, M.S.Ramaiah Institute of Technology, Bangalore, 560080, INDIA CCAR, CPRI, Bnagalore-560080, INDIA

国际会议

第九届电介质材料性能与应用国际会议(The 9th International Conference on Properties and Applications of Dielectric Materials)

哈尔滨

英文

73-76

2009-07-19(万方平台首次上网日期,不代表论文的发表时间)