The Characteristic of Concrete Polluted Composite Insulators
Composite insulators have been widely used in contaminated area because of their excellent antipollution performance. However, some flashover faults of composite insulators were also caused by contamination, especially the composite insulators being used around cement plant. In the paper, the electrical properties and hydrophobicity of different concrete deposit density polluted composite insulators were analyzed in laboratory. The result shows that the flashover voltage decreased with the increase of the concrete deposit density and there is a power function between flashover voltage and concrete deposit density whenever the insulators were polluted for ten days or just for ten minutes. The hydrophobicity of the concrete polluted composite insulators increased with the pollution time and decreased with concrete content.
composite insulator concrete pollution hydrophobicity flashover voltage
Fochi Wang Chengrong Li Yuqian Zhao Yongjiang Bi Bo Zhang
Beijing Key Laboratory of High Voltage & EMC, North China Electric Power University, Beijing, 102206 Beijing Key Laboratory of High Voltage & EMC, North China Electric Power University, Beijing, 102206 Department of electrical engineering, North China Electric Power University, Baoding, 071003, China