Noise Rejection Strategy and Ezperimental Research on Partial Discharge at DC Voltage
Partial discharges (PD) in HVDC equipment are not the predominant degradation factor. However, they can be a failure precursor (particularly when electrical trees are formed), so that monitoring PD could be a tool to infer imminent failures. In order to monitor PD on site, one major problem at DC voltage is the absence of tools able to distinguish noise from PD signals. In this paper, corona, surface and internal discharges measured under DC voltage are extracted from noise and interference resorting to a new strategy of noise rejection at DC voltage.
partial discharge DC voltage noise rejection cross correlation analysis