会议专题

The Equivalent Investigation of Natural Contamination and Artificial Contamination Test

In order to study how the factors (NSDD, distribution of nastiness, components of salt, etc) influenced the flashover characteristics of insulators, the artificial contamination tests were carried out for composite insulators in the conditions of different non-soluble deposit density (NSDD) and different distribution of nastiness and different components of salt in the area of high-altitude Kunming. The paper concludes that the relationship between the coefficient of modifiability of NSDD and NSDD was a negative power function in the condition of equivalent salt deposit density (ESDD) remained constant and the NSDD of insulators was no more than 1.0 mg/cm2; the flashover voltage increased with the degree of un-uniform pollution distributing in the condition of NSDD remains constant; the relationship between the coefficient of modifiability of the different components and the proportion of CaSO4 was an exponent function in the condition of ESDD remained constant. These results would be useful in calculating the DC flashover voltage of composite insulators in the condition of natural contamination, and can also be treated as basis for outdoor insulator selection of transmission lines.

Deposit density Distributing of nastiness Components of salt DC flashover voltage

Gongmao PENG Zhicheng GUAN Fuzeng ZHANG Liming WANG

Graduate School at Shenzhen, Tsinghua University, Shenzhen, 518055, CHINA Department of Electrical E Graduate School at Shenzhen, Tsinghua University, Shenzhen, 518055, CHINA

国际会议

第九届电介质材料性能与应用国际会议(The 9th International Conference on Properties and Applications of Dielectric Materials)

哈尔滨

英文

1000-1003

2009-07-19(万方平台首次上网日期,不代表论文的发表时间)