THE EXPERIMENTAL STUDY ON HEAT TRANSFER CHARACTERISTICS OF THE EXTERNAL HEAT EXCHANGER

Using the external heat exchanger in large-scale CFB boilers can control combustion and heat transfer separately, make the adjustments of bed temperature and steam temperature convenient. The state of gas-solid two phase flow in the external heat exchanger is bubbling fluidized bed, but differs from the regular one as there is a directional flow in it. Consequently, the temperature distribution changes along the flow direction. In order to study the heat transfer characteristics of the water cooled tubes in the bubbling fluidized bed and ensure the uniformity of heat transfer in the external heat exchanger, a physical model was set up according to the similarity principle and at the geometric ratio of 1:28 to an external heat exchanger of a 300MW CFB boiler. The model was connected with an electrically heated CFB test-bed which provides the circulating particles. The influencing factors and the distribution rule of the particles’heat transfer coefficient in the external heat exchanger were assessed by measuring the temperature changes of the water in the tubes and different parts of particles flow along the flow direction. At the end, an empirical correlation of particles’heat transfer coefficient in external heat exchanger was given by modifying the Veedendery empirical correlation.

CFB ezternal heat ezchanger heat transfer coefficient temperature distribution directional flow

X.Y.Ji X.F.Lu L.Yang H.Z.Liu

School of Power Engineering of Chongqing university, Chongqing, 400044, China

国际会议

第20届国际流化床燃烧会议(20th International Conference on Fluidized Bed Combustion)

西安

英文

373-378

2009-05-18(万方平台首次上网日期,不代表论文的发表时间)