Study on the Optimal Control of Mized-pump Stations and the Operating-mode Adaptability for Water Supply System Based on Security
At present, fixed speed pumps and variable speed pumps always run in parallel in pump stations of most water supply companies in China. Research on the frequency control characteristic for the mixed-pump station based on the two-stage optimal operation is performed. Firstly, the ratio of the variable speed pump is calculated inversely according to the outlet pressure of the pump station, and then the speed range can be determined dynamically, so that the variable speed pump can play the role of energy saving as far as possible in safe and rational running status. Secondly, the two-stage optimal operation model for mixed-pump stations of multi-source is established, which is of the operating-mode adaptability, and it is solved by the intelligent genetic algorithm. Furthermore, when the operation mode of multi-source pump stations is transformed, the optimal dispatching of water distribution system in corresponding operation mode can be realized through adjusting the variable parameters in the model. At last, the utility and superiority of the optimal operation method for mixed-pump stations of multiple resources is verified by means of the application in certain urban in China.
Mized-pump stations of multiple resources Dynamic determination of speed range Operating-mode adaptability Intelligent genetic algorithm
Lu Mou Dong Shen Ren Li
Qingdao Technological University, Qingdao 266033, China Maanshan Capital Water Co.Ltd., Maanshan 243000, China
国际会议
第八届中日水环境暨NSFC-JST重大国际合作项目成果交流会
苏州
英文
100-107
2008-11-29(万方平台首次上网日期,不代表论文的发表时间)