Performance Evaluation of a Solar Energy Water Heater in Conjunction with Air Source Heat Pump
In order to extend the annual operation time of solar energy water heating system, a solar energy water heater in conjunction with air source heat pump (SEWH-ASHP) is designed. In the SEWHASHP,the solar energy water heater incorporates with the heat pump through a hot water storage tank.Based on the component design and system matching, a flat-plate solar energy water heater with 320m2 collector areas in conjunction with four air source heat pump units was built for practical applications in Kunming, Yunnan Province of China. For the SEWH-ASHP, the solar collectors can provide about 81% heat loads during the entire year.The COP(coefficient of performance) of the air source heat pump units varies within the range of 2.5-3.3 during the coldest month,January, with a monthly average temperature 7.2℃.
Luo H L Peng J H Zhong H Leng T T
Faculty of Architecture Engineering,Kunming University of Science and Technology,Kunming 650224,P.R. Faculty of Materials and Metallurgical Engineering,Kunming University of Science and Technology,Kunm Institute of Solar Energy,Yunnan Normal University,Kunming 650092,P.R.China