Energy Savings Effect of a Novel Passive Air Dehumidification Unit
Concerns on indoor air quality have prompted the researches of novel air dehumidification techniques. This study proposed a new passive air dehumidification system, membrane-based total heat exchanger in which the fresh air is cooled and dried by the exhaust air in summer. To improve performance, a novel concept of composite supported liquid membrane (CSLM) combined with a cross-corrugated triangular duet structure is proposed. The sensible and latent effectiveness are calculated from heat mass transfer correlations.The total heat exchanger based on this concept has a sensible effectiveness of 0.82, and a latent effectiveness of 0.64, which are far higher than current commercial products. Besides, a total of 12.4% energy for air conditioning could be saved with this technology annually.
Zhang L Z Liang C H
Key Laboratory of Enhanced Heat Transfer and Energy Conservation of Education Ministry,School of Chemical and Energy Engineering,South China University of Technology,Guangzhou 510640,P.R.China
国际会议
上海
英文
733-736
2008-04-05(万方平台首次上网日期,不代表论文的发表时间)