Economical Match of Radiators and Water Source Heat Pump Hybrid Heating System

A plan was adopted using existing clean geothermal energy to satisfy the heating demand (mainly for animals) of Tianjin Zoo in winter.A hybrid heating system was proposed.In this system,the geothermal water is first pumped to each house through the pipe network,flowing through the existing radiators.Then after releasing heat,the tail water goes into the water source heat pump to discharge more heat.Finally,when its temperature is about 10 degrees Centigrade,the tail water is discharged.BIN method was used to calculate the heat load of the whole heating seasons.Life cycle costs of three running modes were analyzed.Mode Ⅰ with return water temperature of 33 degrees Centigrade was found to be the most economical scheme with a total fee of 5.6 million Yuan,while costs of mode Ⅱ and mode Ⅲ were 6.13 and 7.1 million Yuan,respectively.The economical match of the radiators and heat pump was determined according to the outlet flow temperature of the radiator,namely,33 degrees Centigrade.

Radiator Water source heat pump Geothermal water Life cycle cost BIN

Hejiang Sun Yunxia Zhang Shijun You

School of Environmental Science and Technology,Tianjin University,Tianjin,China Tianjin Municipal Engineering Design & Research Institute,Tianjin,China

国际会议

The First International Conference on Building Energy and Environment(第一届建筑能源与环境国际会议)

大连

英文

2064-2069

2008-07-01(万方平台首次上网日期,不代表论文的发表时间)