会议专题

Experimental Studies of Direct Evaporation Ice-on-coil with Variable Coil Arrangement Density

In order to study the influence of the direct evaporation coil arrangement density on the characteristic of the direct evaporation ice-on-coil thermal storage system.A direct evaporation ice-on-coil thermal storage experimental platform was set up with the directevaporation coil arrangement density changeable.The direct evaporation ice-on-coil was designed with the copper tube of diameter 16mm and wall thickness 1mm and it can be arrayed at high arrangement density,middle arrangement density or low arrangement density in the ice storage bank.The ice storage and heat releasing experiments were done at the three kinds of coil arrangement density.The experimental results show that with the increasing of the ice arrangement density,the characteristic of the thermal storage system performance improved markedly.The high arrangement density system shortens about 2~3 hours of ice storage at the same storage capacity and the average heat releasing rate of the high arrangement density system is 1.8 times the low arrangement density coil system at the same ice storage quantities,chilled backwater temperature and the flux.

Direct evaporation Ice-on-coil Ice thermal storage Heat releasing

Yin Liu Guanghui Zhou Angui Li Xiaofei Xu

School of Energy & Environmental,Zhongyuan University of Technology,Zhengzhou,China School of Enviro School of Energy & Environmental,Zhongyuan University of Technology,Zhengzhou,China School of Environmental & Municipal Engineering,Xian University of Architecture and Technology,Xia

国际会议

The First International Conference on Building Energy and Environment(第一届建筑能源与环境国际会议)

大连

英文

1567-1573

2008-07-01(万方平台首次上网日期,不代表论文的发表时间)