会议专题

Investigation on Air-flow Fields in Air Side Heat Exchanger of an Air Source Heat Pump Heater/Chiller

The three dimensional air-flow fields in the air side heat exchanger of an air source heat pump heater/chiller was studied by computational fluid dynamics(CFD).Numerical results were testified by the experiments.The influence of intersect angle and average face velocity on the air-flow fields were investigated respectively,the results showed the followings: the face velocity distribution along the heat exchanger height was non-uniform; The air-flow fields was determined by the heat exchanger construction; The air flow maldistribution might affect the fin using life; The intersect angle value was the main factor affecting the air velocity malditribution degree.When the intersect angle was 90,the air velocity maldistribution degree was the least; The maximum of air velocity moved downwards along the heat exchanger height direction with intersect angle increasing.The maximum of air velocity occurred at the middle location of heat exchanger when the intersect angle was 90.

V-type fin-tube heat exchanger Face velocity Intersect angle Air flow maldistribution

Jianying Gong Xiuling Yuan

School of Refrigeration and Cryogenics,Xian JiaoTong Univerdity,Xian,China

国际会议

The First International Conference on Building Energy and Environment(第一届建筑能源与环境国际会议)

大连

英文

1529-1536

2008-07-01(万方平台首次上网日期,不代表论文的发表时间)