会议专题

The Impact of Urban Heat Island Effect on Office Buildings Cooling Load

Air temperature of 6 points in the summer in Tianjin city show that the average Urban Heat Island (UHI) intensity is about 3-5 ℃.In addition,the data indicates different urban area has different local UHI because of unbalanced development.With the help of Building energy consumption simulation software Energy Plus,the paper analyzed the extent of influence of UHI intensity on office building cooling load in different area of Tianjin city and discussed the influence of UHI on cooling load of office buildings with different envelope thermal property.The results disclosed that the UHI increased the peak cooling load of downtown office building up to 5.71%.The building envelope thermal sensitivity enhances the effect of heat island on buildings cooling load: when UHI intensity increases 1 ℃,sensitive buildings cooling load increases 2.82%,and insensitive building increases 2.21%.

Urban heat island effect Building energy simulation Cooling load Thermal property

Zhe Tian Qingqin Wang Neng Zhu Peng Peng

School of Environmental Science and Technology,Tianjin University,Tianjin,China China Academy of Building Reasearch,Beijing,China Beijing Architecture Design and Research Institute,Beijing,China

国际会议

The First International Conference on Building Energy and Environment(第一届建筑能源与环境国际会议)

大连

英文

293-300