Wall Temperature Calculation of Drum for Large Capacity Boiler
Drum wall temperature calculation is the key point in the low cycle fatigue analysis. We used to use the formula〔δT = 1/aΦVS2(former Federal Germany standard TRD 301 Annex 1) to calculate the wall temperature difference, and the results were too high to analyze the fatigue. The article starts from the 2D thermal conductive equation, and get the amendatory formula〔δT=-ΦVS2(1-l-μ-τt/a. Using this formula we get reasonable results in many drum wall temperature calculation.
Low cycle fatigue Wall temperature difference Sub-steady temperature Field
WU RU SONG
Design department, Shang Hai Boiler works Ltd.
国际会议
2007杭州国际动力工程会议(The International Conference on Power Engineering 2007)
杭州
英文
2007-10-23(万方平台首次上网日期,不代表论文的发表时间)